UPS SLC 5000 TWIN PRO2 B1 double-conversion 4 to 10kVA

 

Enhanced protection for mid-range systems with single-phase power supply

 

Salicru's SLC 5000 TWIN PRO2 5kVA UPS features on-line double conversion technology, currently the most advanced for the protection of critical systems as it provides a fully stabilised and filtered sinusoidal supply voltage.

 

The Salicru SLC TWIN PRO2's output voltage is always single-phase, featuring a single-phase input of 5 kVA. The SLC 5000 TWIN PRO2 5kVA UPS provides a unitary output power factor, the most optimum for systems and environments with high energy needs. Adaptability is another important feature thanks to the numerous operating modes available: On-line, Batteries, Eco-mode, Bypass, Frequency converter and Parallel redundant.

 

The possibilities of control and monitoring are varied: on the one hand, an LCD display + keypad for local operation of the device, and, on the other, various communication options (USB HID and RS-232 interfaces, and slot for SNMP, RS-485 and AS-400 cards) that enable the UPS to be integrated into standard or virtualised platforms for management, incident notification and remote maintenance.

 

 

Features


  • On-line double conversion and DSP control technology.
  • Output power factor PF=1
  • Compact tower format for space saving.
  • Active power factor corrector for all input phases.
  • Multiple operating modes for better adaptability.
  • Equipped for parallel operation as standard, up to 3 devices.
  • USB and RS-232 interface for all models as standard.
  • Monitoring software for Windows, Linux, Unix and Mac.(downloadable)
  • Intelligent slot for SNMP/RS-485/optocoupler cards.
  • Eco-mode operation for increased efficiency.
  • Backup extensions available for all power ratings.
  • Frequency conversion function.
  • EPO – emergency power off.
  • Manual and/or automatic programmable battery test.
  • SLC Greenergy solution.

 

 

Operating Modes

 

On-line double-conversion

Double voltage conversion (AC/DC + DC/AC), providing the best degree of safety to loads

 

 

Bypass

In the event of any eventuality (incident, overload, etc.), the loads continue to be powered by the input voltage.

 

 

Eco-Mode

Increased efficiency up to 99%, with immediate availability of full power.

 

 

 

Batteries

In the event of power failure, the loads continue to be powered by means of batteries

 

 

Frequency Converter

Adaptation of the output frequency to the needs of the load (50/60 Hz or 60/50 Hz).

 

 

Parallel Redundant

Increased safety (N+1) or capacity, with configurations of up to 3 devices.

 

 

 

Applications

 

Salicru's SLC TWIN PRO2 series is the best option for providing a secure power supply to ERP systems, Business Intelligence, CRM solutions, intranets/extranets and corporate networks in the event of a wide range of possible disturbances (micro power outages, voltage fluctuations, frequency variations, harmonics, transients, etc.), which can cause irreparable damage or incur high costs in all of these critical systems.

 

 

Technical Specification

 

 

UPS Power (VA / W) 5000 / 5000
Technology On-line, double conversion, PFC with double DC bus
Format Tower
Input Rated Voltage 208 / 220 / 230 / 240 V (1)
Voltage range 110 ÷ 276 V (2)
Total harmonic distortion (THDi) <4%
Power Factor ≥0.99
Frequency 50 / 60 Hz ±10%
Input protection Resettable breaker
Output Rated voltage 208 / 220 / 230 / 240 V (1)
Voltage accuracy (battery mode) ±1%
Power factor 1
Total harmonic distortion (THDv) ≤1% linear load;
≤4% non-linear load
Performance (normal mode) 93% ÷ 94%
Permissible overloads
(normal mode)
Up to 110% for 10 min;
130% for 1 min
Parallel Yes, up to 3 units (3)
Synchronisation with mains ±4 Hz
without mains ±0.1 Hz
Programmable priority outputs No
Crest factor 3 to 1
Manual Bypass Yes
Bypass Type Hybrid
Transfer time Nil
Battery Battery type Pb-Ca sealed, AGM, maintenance-free
Protection Against power surges, undervoltages and alternating current components
Charging Charge type I/U (constant current/constant voltage)
Recharge time 7-9 hours to 90%
Temperature voltage compensation Yes
Communication Interface USB, RS-232 and relay
Intelligent slot Yes, ready for SNMP / AS400 / RS485-Modbus
Downloadable monitoring software For Windows, Unix, Linux and Mac
Other Functions Eco-mode 4 Yes
Frequency converter Yes (4)
Cold start Yes
General Operating temperature 0ºC - 40ºC
Relative humidity Up to 95%, non-condensing
Noise level at 1 metre  Less than 60dB
Dimensions (D x W x H mm) 592 x 250 x 576
Weight 82Kg
Standards Safety EN 62040-1; EN 60950-1
Electromagnetic compatibility (EMC) EN 62040-2 Category C3
Operation VFI in accordance with EN 62040-3
Quality & Environmental Management ISO-9001 and ISO-14001

(1) Power reduction to 90% for 208 V input
(2) With 50% load
(3) Power reduction to 90%
(4) Power reduction to 60%